●Electronically addressed, unique ID, can be addressed by controller or hand held programmer,
automatic log in, easy for installation and commissioning.
●Fire LED allows 360° viewing.
●Software specially strengthened anti-jamming measures, all with the actual fire to heat up the case
of interference by different software screen.
●Can detect sensor fault (short circuit or open circuit), the failure rate is low, long service life.
·
Working temperature: -10℃
~ +50 ℃
·
Working humidity: ≤95% RH (No condensation of moisture)
·
Working wire voltage: DC24V Pulsating voltage
·
Operating temperature: 56℃~ 66℃ (56℃ by default)
.Alarm indicating lamp:Red,flickers during routing inspection,keeps lighting during alarming
· Standby current: <0.35mA
· Alarming current: <0.8mA
· Monitoring area: 20m2
· Wiring system: Two-wire
bus, non-polarized
· Bus length: ≤2000m
· Cleaning of detector:
Rotatable, detachable
· Color: EI White