Location: Home > Products >  Automatic Fire Alarm and Linkage Control System >  Modules
Products
Broadcast System Repeater Controller Modules Sound and Light Alarm Detector The Internet Manual Call Point Telephone System Power Supply Explosion-Proof Series
Input Module(J-EI6031)
Product Overview:

(1)Dual input; receives alarm signals from passive normally-on/off monitors such as pressure switch, water flow indicator, flammable gas detector, independent detector for electric fire protection, as well as operating signals from linkage equipment such as 280°C fire-resisting damper. Both inputs have the “operating” indicators directly indicate the statuses of alarming/operating.

  (2)  A protective circuit is added to the signal detection area to avoid incorrect wiring or damage of the module caused by short circuit. As for equipment that provides passive normally-on alarm signals, the input module may detect the shut-off failure of its attached equipment when load resistance is connected in the contact spots, ensuring system stability and reliability.




. Electronically encoded with only one ID; online addressing by controller or addressing by encoder; automatic log-in, convenient installation and debugging.

· A CPU and smart software are built in, high smartness level.

· Convenient wiring, good-looking appearance, suitable to DH86 junction box.

 

 


 · Working temperature:-10℃ ~+50℃

 · Bus working voltage: 24V Pulsating voltage

 · Standby current:<0.35mA

 · Operating current:<0.8mA

· Alarm indicating lamp: Red, flickers during routing inspection, keeps lighting during alarming

· Carried standard:GB16806-2006 Fire-Fighting Linkage Control System

· Working humidity: <95% RH (No condensation of moisture)

· Wiring system: Two-wire bus (non-polarized)

· Bus length: ≤2000m

· Load resistance: 1/4W  47kW

· Protection level of casing: IP30

Back
Contact Us
eifire@eifire.com
400-0552-119
Contact Us400-0552-119
Follow Us Follow Us