(1) .Both the input and output ends are independently programmable, which can be used separately or jointly.
(2) .Able to detect shut-off failures of signal input wire and module output wire of equipment.
· Electronically encoded with only one ID; online addressing by controller or addressing by encoder; automatic log-in, convenient installation and debugging.
· Able to detect shut-off failures of 24V.
· Brand new plug-type design, convenient installation and wiring.
· Multiple-address programming, able to perform multiple functions on one component, cost-saving.
· Working temperature: -10℃ ~ +50 ℃
· Bus working voltage: DC 24V Pulsating voltage
· power supply: DC 24V±1015%
· Standby current: <0.4mA (bus); <2.0mA (DC24V)
· Operating current: <2mA (bus); <25mA (DC24V)
· Working humidity: <95% RH (No condensation of moisture)
· Wiring system: Two-wire bus
· Bus length: ≤2000m
· Protection level of casing: IP30
· Relay contact: One set normally-on/off, DC30V/1A
· Input & output end: Independent, programmable
· Relay contact: One set normally-on/off, DC30V/1A
· Input & output end: Independent, programmable