Intrinsically safe type, non-addressable, multiple
parallel connection S2004 Zener barrier and J-EI6032/EI6034 type relay module
are connected to EI series fire alarm controller and fire alarm controller
(linkage type).
• Explosion-proof mark: ExibIICT6 Gb
• Original rotating structure for easy
installation.
• Reset with a dedicated key.
• Provide a set of passive normally open
points.
• Ambient temperature: -10C~+55C
• Operating voltage: powered by the safety barrier
• standby current: <0.2mA
• Fire alarm light: red
• Wire system: two-wire system, no polarity
• Explosion-proof mark: ExibIICT6 Gb
• Associated equipment: S2004 Zener barrier
• Ambient humidity: <95% RH (non-condensing)
• Internal button contact capacity: DC24V/0.1A
• Alarm current: <0.8mA
• Inspection light: green (cycle flashing)
• Shell protection rating: IP30
• Intrinsically safe explosion-proof parameters: Ui: 28VDC Ii: 93mA
Pi: 0.65W Ci: 0.02∞F Li: 0 mH
• Executive Standard: GB19880-2005 《Manual call point 》, GB 3836.1-2010《Explosive Environment Part 1: General Requirements for Equipment》, GB 3836.4-2010 《Explosive Environment Part 4: Protected by Intrinsic Safety "i" device》